APPLICATIONS
Water lifting sets particularly suited for domestic use, and small civil, agricultural, or industrial systems. Their main features are utmost reliability, simple
operation, and the fact that no maintenance is required. The sets are supplied as standard with tanks and with air supply connector.
TECHNICAL DATA
Operating range: from 1 to 14.5 m3
/h.
Pumped liquid: clean, free of solids and abrasives, non
viscous, non aggressive, non crystallised and chemically neutral,
with properties similar to water.
Pumped liquid temperature range: from 0 °C to +35 °C for domestic
use – +40 °C for other uses.
Maximum ambient temperature: +40°C.
Maximum operating pressure: PN10.
Special executions on request: contact our sales network.
Protection class: IP44.
IE2 motors as standard from 0,75 kW to 5,5 kW – IE3 ≥ 7,5 kW.
CONSTRUCTION FEATURES
HYDRAULIC SECTION
2 EURO multistage centrifugal electric pumps. Tropicalized galvanized sheet steel base complete with 4 rubber anti-vibration feet. Suction and delivery
manifolds in tropicalized galvanized steel. 2 membrane tanks. Ball valves with unions on the suction and delivery ports of each pump. Check valves on
the suction port of each pump. 1 1/4″ air supply connection at the suction of each pump. 2 tropicalized galvanized cast iron female plugs for closing the
manifolds. 1 pressure transmitter on the delivery manifold (pressure detection).
ELECTRICAL SECTION
Supplied in an IP 55 protection class self-extinguishing thermoplastic material box, the control panel protects the electric pumps from abnormal
conditions such as: overload and overtemperature (with automatic reset), short circuit (with fuses – Plus model only), pump current surges (amperometric
protection), abnormal voltage, dry run, quick starts, pressure sensor fault, or inconsistency of the external protection commands.
FRONT PANEL COMPONENTS:
General disconnector with padlockable door lock. AUT-0-MAN operation selection pushbuttons. Alarm RESET pushbutton. Display for all models.
Operation, stop, alarm notification lamps.
PANEL INTERNAL COMPONENTS:
Electronic control card with protection fuses and contactors. Power input connection terminal (single phase or three phase). Dry run or overpressure
pressure switch connection terminals (optional). Alarm notification N.O. contacts. Function selection mini dip switch (pressure transmitter or pressure
switches, standard or additional tanks).
The electric control panel is ready for the connection of:
Dry run protection float or pressure switch kit (*).
Overpressure stop pressure switch kit (*). available separately as optional.
The sets are supplied in a sturdy cardboard packaging on wooden pallet and installation / maintenance manual with electric diagram.